Pokud potřebujete pomoc, prosím klikněte zde:

NetCol8000-C In-Room Chilled Water Smart Cooling Products

The NetCol8000-C series of smart cooling products provides a complete in-room, chilled-water cooling system, combining chillers, chilled-water pumps, and pipes. Offering extreme reliability, the series is designed for medium- to large-sized Data Centers (DCs) in a variety of sectors.

Using a modular design, NetCol8000-C can be disassembled without on-site welding, and be moved through standard-sized doors and elevators. Main control and auxiliary power modules are hot-swappable, for fast maintenance, while self-diagnosis functionality intelligently eliminates irrelevant failures.

Equal-enthalpy humidification technology removes the need to heat water, in turn reducing humidifying power consumption per kilogram to less than 50 W — a dramatic reduction of 95% compared to electrode and infrared humidifiers.
Huawei

Specifications



Unit Model NetCol8000-C070D NetCol8000-C130D NetCol8000-C190D
Total Cooling Capacity¹ 63.2 kW 126.4 kW 189.6 kW
Sensible Cooling Capacity 51.4 kW 102.8 kW 154.2 kW
Air Flow 13,500 m3/h 27,000 m3/h 40,500 m3/h
Power Supply 380–415 V, 3 phase, 50 Hz 380–415 V, 3 phase, 60 Hz 440–480 V, 3 phase, 60 Hz
Water Flow 3.02 L/s 6.03 L/s 9.05 L/s
Water Pressure Drop 62.4 kPa 85.4 kPa 96 kPa
Heating Capacity 6 kW 12 kW 12 kW
Humidifier Capacity 5 kg/h 8 kg/h 12 kg/h
Full Load Current² 4.7 (15.2) A 8.9 (29.9) A 13.1 (34.1) A
Dimensions (H x W x D) 2000 x 900 x 1000 mm 2000 x 1800 x 1000 mm 2000 x 2700 x 1000 mm
Net Weight 340 kg 635 kg 930 kg

Notice:

1. Nominal cooling condition: 24°C return air dry bulb temperature, 50% relative humidity, 7°C/12°C inlet/outlet water temperature, 20 Pa Electrical Submersible Pump (ESP).

2. The numbers in parentheses are applicable to units with electric heaters and humidifiers.nlet/outlet water temperature, 20 Pa Electrical Submersible Pump (ESP).

Unit Model NetCol8000-C070U NetCol8000-C130U NetCol8000-C190U
Total Cooling Capacity¹ 61.9 kW 123.8 kW 185.7 kW
Sensible Cooling Capacity 50.3 kW 100.6 kW 150.9 kW
Air Flow 13,200 m3/h 26,400 m3/h 39,600 m3/h
Power Supply 380–415 V, 3 phase, 50 Hz 380–415 V, 3 phase, 60 Hz 440–480 V, 3 phase, 60 Hz
Water Flow 2.95 L/s 5.91 L/s 8.86 L/s
Water Pressure Drop 60.5 kPa 82.6 kPa 92.7 kPa
Heating Capacity 6 kW 12 kW 12 kW
Humidifier Capacity 5 kg/h 8 kg/h 12 kg/h
Full Load Current² 4.7 (15.2) A 8.9 (29.9) A 13.1 (34.1) A
Dimensions (H x W x D) 2000 x 900 x 1000 mm 2000 x 1800 x 1000 mm 2000 x 2700 x 1000 mm
Net Weight 330 kg 615 kg 900 kg

Notice:

1. Nominal cooling condition: 24°C return air dry bulb temperature, 50% relative humidity, 7°C/12°C inlet/outlet water temperature, 20 Pa Electrical Submersible Pump (ESP).

2. The numbers in parentheses are applicable to units with electric heaters and humidifiers.nlet/outlet water temperature, 20 Pa Electrical Submersible Pump (ESP).

Pro partnery

Pokud jste již partnerem, klikněte sem a získáte další marketingové zdroje.
Klikněte sem a navštivte zónu pro partnery a zkontrolujte stav dotazu, spravujte objednávku, získejte podporu nebo zjistěte víc o Huawei Partners.