Amennyiben segítségre van szüksége, kattintson ide:

PowerPod Solution (FusionPower 6000)

The PowerPod Solution (FusionPower 6000) integrates full-power links from the medium-voltage transformer to the load feeder, to provide MW-level integrated power supply, distribution, and backup solutions for large data centers.

Huawei

Specifications

Parameters FusionPower6000-2.4 MVA (Indoor) FusionPower6000-2.0 MVA (Indoor) FusionPower6000-1.6 MVA (Indoor) FusionPower6000-1.2 MVA (Indoor)
Power Supply and Distribution Power Input 380/400/415 V AC, three-phase four-wire + PE, 50/60 Hz
Transformer 2500 kVA 2000 kVA 1600 kVA 1250 kVA
SVG 500 kVAR 400 kVAR 300 kVAR 250 kVAR
UPS 2 x UPS5000-H-1200k 2 x UPS5000-H-1000k 1 x UPS5000-H-1600k 1 x UPS5000-H-1200k
Branch Feeder 3 x feeder cabinets (7 x 400 A 3P) 3 x feeder cabinets (7 x 400 A 3P) 2 x feeder cabinets (7 x 400 A 3P) 2 x feeder cabinets (7 x 400 A 3P)
Monitoring Power Monitoring System ECC for centralized management
Structure External Dimensions (H x W x D) 3002 x 12,800 x 1650 mm 3002 x 12,700 x 1650 mm 2475 x 9300 x 1500 mm 2475 x 8350 x 1450 mm
Installation Mode Direct installation on the ground.
Assembly and installation onsite at the base.
Environmental Requirements Operating Temperature 0°C to 40°C
Storage Temperature –40°C to +70°C
Ambient Humidity ≤ 95% RH (non-condensing)
Application Environment Class A environment
Altitude 0–4000 m. When the altitude is greater than 1000 m, the power is derated according to the industry standard.