Requêtes
This site uses cookies. By continuing to browse the site you are agreeing to our use of cookies. Read our privacy policy>
In-room, air cooled NetCol8000-A smart cooling products are suitable for small- and medium-sized Data Centers (DCs), power distribution rooms, and small computer rooms.
Configured with a high-efficiency DC inverter compressor, Electronically Commutated (EC) fan, and Electronic Expansion Valve (EEV) for on-demand cooling, NetCol8000-A provides energy savings of more than 30% at partial load, compared to fixed-frequency systems, helping build next-generation, green data centers.
Offering stepless capacity with high efficiency at partial load, plus operation without heated water, NetCol8000-A offers energy savings of more than 95% compared to electrode humidifiers.
The NetCol series of cooling products have been deployed around the world, and are used in carrier, Internet Service Provider (ISP), government, finance, transportation, energy, medical, and education sectors.
By using a high-efficiency DC inverter compressor, EEV and EC fans, stepless capacity regulation, and cooling on-demand technologies, the product provides energy savings of more than 30% at partial load compared to a fixed-frequency system.
Equal-enthalpy humidification technology eliminates the need to use heated water, with humidifying power consumption per kilogram reduced to less than 50 W, providing energy savings of up to 95% compared to electrode humidifiers and infrared humidifiers.
6kV surge protection ensures the cooling product’s consistent reliability, even in extreme conditions.
Unit Model | Uniit | NetCol8000-A045D/U | NetCol8000-A060D/U | NetCol8000-A090D | NetCol8000-A120D |
Air Discharge Direction | - | D: Downflow; U: Upflow | |||
Total Cooling Capacity1 | kW | 45 | 60 | 90 | 120 |
Sensible Cooling Capacity | kW | 45 | 60 | 90 | 120 |
Air Volume | m3/h | 11250 | 14500 | 22500 | 29000 |
Power Supply | V/Ph/Hz | 380/400/415Vac, 50/60Hz, 3Ph+N+PE | |||
Heating Capacity2 | kW | 6 | 6 | 12 | 12 |
Humidifier Capacity2 | kg/h | 4.5 | 6 | 10 | 10 |
Full Load Current | A | 36(40) | 41(45) | 72(80) | 82(90) |
Dimension: W×D×H | mm | 900*900*2000 | 1100*1000*2000 | 1800*1000*2000 | 2200*1000*2000 |
Net Weight | kg | 355 | 400 | 643 | 772 |
Remarks: 1. Nominal condition: indoor return air 35ºC/26%RH, outdoor 35ºC. 2. The current data in brackets are applicable to the indoor unit with electric heater & humidifier (Optional). 3. NetCol8000-A045 and NetCol8000-A060 is a single-system unit. NetCol8000-A090 and NetCol8000-A120 is a dual-system unit. |
Unit Model | NetCol8000-A013U |
Air Discharge Direction | Upflow |
Total Cooling Capacity¹ | 13 kW |
Sensible Cooling Capacity | 11.7 kW |
Air Volume | 3600 m3/h |
Power Supply Voltage | 380–415 V, 3 phase, 50 (60) Hz |
Refrigerant | R410A |
Heating Capacity (Optional) | 4 kW |
Humidifier Capacity (Optional) | 3 kg/h |
Dimensions (H x W x D) | 1886 x 800 x 664 mm |
Net Weight² | 141 (153) kg |
Notice:
1. Nominal cooling condition: 24°C return air dry bulb temperature, 50% relative humidity, 35°C outdoor temperature.