NetCol8000-C In-room Chilled Water Precision Air Conditioner

NetCol8000-C in-room chilled water PAC is a cooling terminal used for medium to low power density, medium to large DCs. The NetCol8000-C is usually combined together with a chiller, water pump, cooling tower to form a precision DC environment control system. It builds an efficient, reliable, and simple cooling solution. The cooling capacity covers from 62 kW to 253 kW.

Build an efficient, reliable, and simple data center

  • Simple: Unique malfunction self-diagnosis simplifies O&M and reduces waiting and maintenance time by 7+ hours
  • Efficient: Unique wet-film humidifier saves 95%+ of energy compared to an electrode or infrared humidifier
  • Reliable: Hot-swappable control module and auxiliary power module allows online replacement in 1 minute and increases the Mean Time Between Failures (MTBF) by 20%+

Specifications

Model

NetCol8000-C070D

NetCol8000-C130D

NetCol8000-C190D

Air Direction

Downflow

Total Cooling Capacity

63.2 kW*

126.4 kW*

189.6 kW*

Sensible Cooling Capacity

51.4 kW*

102.8 kW*

154.2 kW*

Air Flow

13,500 m3h

27,000 m3h

40,500 m3h

Power Supply

380V to 415V/3 Ph/50 Hz, 380V to 415V/3 Ph/60 Hz, 440V to 480V/3 Ph/60 Hz

Water Flow

3.02 liters per second

6.03 liters per second

9.05 liters per second

Water Pressure Drop

62.4 kPa

85.4 kPa

96.0 kPa

Heating Capacity

6 kW

12 kW

12 kW

Humidifier Capacity

5 kg/h

8 kg/h

12 kg/h

Full Load Current

4.7A (15.2A)**

8.9A (29.9A)**

13.1A (34.1A)**

Dimensions: W x D x H

900 mm x 1,000 mm x 2,000 mm

1,800 mm x 1,000 mm x 2,000 mm

2,700 mm x 1,000 mm x 2,000 mm

Net Weight

340 kg

635 kg

930 kg

Notes:

* Cooling capacity condition: Return air DB temperature 24°C/RH50%, inlet/outlet water temperature 7°C/12°C, static pressure 20 Pa
** The current data in brackets are applicable to the unit with a electric heater and humidifier